Pool electrical bonding practice questions

35 questions from the Swimming pool contractor practice test.

Start practising

Pool electrical bonding practice test

10 questions, graded as you go, with the reason for every answer. Start free, no sign-up.

Sample questions

Under NEC 2023, what is the maximum length of the flexible cord on a cord-and-plug connected pool pump?

  1. 3 feet
  2. 6 feet
  3. 10 feet
  4. 25 feet
Show the answer

A. 3 feet

Cord-and-plug connection of stationary pool equipment is allowed for easy removal for maintenance, but the cord is limited to 3 ft (0.9 m) and needs a copper grounding conductor and a grounding-type plug. A longer cord would be allowed for portable tools but not for pool equipment.

Reference: NEC 2023, 680.7(A)

Under NEC 2023, what is the smallest conductor normally used to bond the pool shell steel and metal parts to the bonding grid?

  1. 12 AWG stranded copper
  2. 10 AWG stranded copper
  3. 8 AWG solid copper
  4. 6 AWG aluminum
Show the answer

C. 8 AWG solid copper

Bonding conductors for pool bonding are solid copper, 8 AWG or larger. Stranded conductors and aluminum are not what the pool bonding rules call for, and 12 or 10 AWG is smaller than the minimum.

Reference: NEC 2023, 680.26(B)

A new ceiling light will be installed directly over a permanently installed outdoor pool. Under NEC 2023, the fixture must be at least how high above the maximum water level?

  1. 5 feet
  2. 8 feet
  3. 12 feet
  4. 15 feet
Show the answer

C. 12 feet

New luminaires, lighting outlets and ceiling-suspended fans over the pool, or within 5 ft horizontally of its inside wall, must be at least 12 ft above the maximum water level unless the rules for a listed exception apply. Five feet is the horizontal reach of the rule, not the height.

Reference: NEC 2023, 680.22(B)