10 questions, graded as you go, with the reason for every answer. Start free, no sign-up.
Sample questions
A firefighter is using Phase II in-car operation and wants the car to stay at a floor with the doors open while he works. Which key switch position does this?
OFF
HOLD
ON
BYPASS
Show the answer
B. HOLD
The Phase II switch has OFF, ON and HOLD. HOLD keeps the car at the landing with the doors open. ON gives normal in-car control, and BYPASS is a Phase I position.
Why must a permanent pit ladder reach above the access door sill?
So the car cannot run over it
So it can be used as a ground
For handhold when stepping on/off
So the pit can be ventilated
Show the answer
C. For handhold when stepping on/off
Extending the ladder above the sill gives a hand grip at the moment of transition, when falls happen. Ladder length has nothing to do with ventilation or grounding.
NEC 2023 requires GFCI protection for certain receptacles in elevator pits and machine rooms. Which receptacles?
Only 480-volt receptacles
Only receptacles on the car
Only receptacles in the machine room ceiling
125-volt, 15- and 20-ampere receptacles
Show the answer
D. 125-volt, 15- and 20-ampere receptacles
Pits are damp and workers stand on conductive surfaces, so the common 125-volt, 15 and 20 ampere outlets need ground-fault protection. High voltage motor feeders are not what this rule covers.