A Class A pathway between a control unit and its devices suffers a single open on one conductor. What happens?

  1. Signals still arrive over the return path and trouble is shown
  2. Every device past the break is cut off and no trouble is shown
  3. Devices past the break go into alarm until the wire is repaired
  4. The control unit shuts down until the open is found and fixed
Show the answer

A. Signals still arrive over the return path and trouble is shown

A Class A pathway has a return path, so signals can still reach the control unit from both ends of the break while a trouble signal reports the fault. A Class B pathway is the one where devices past an open are cut off, though trouble is still shown.

Reference: NFPA 72 (2025), Chapter 12, circuits and pathways (Class A and Class B)

What is the minimum distance a ceiling smoke detector must be kept from an air supply diffuser under NFPA 72 (2025)?

  1. 6 inches
  2. 12 inches
  3. 18 inches
  4. 3 feet
Show the answer

D. 3 feet

Supply air can dilute or blow smoke past a detector, so detectors are kept at least 3 feet from supply diffusers. The shorter distances do not give enough separation.

Reference: NFPA 72 (2025), Chapter 17, spot-type smoke detector location (air supply diffusers)

The building's primary AC power to a fire alarm control unit fails. What does NFPA 72 (2025) expect the system to do?

  1. Sound an alarm and automatically call the fire department
  2. Transfer to the secondary supply and show a trouble signal
  3. Shut down the initiating circuits to save battery power
  4. Keep running with no indication until the batteries run low
Show the answer

B. Transfer to the secondary supply and show a trouble signal

Loss of primary power is a trouble condition. The unit moves to its batteries and indicates trouble so someone can act before the batteries are used up. It is not an alarm, and the system must not hide the condition.

Reference: NFPA 72 (2025), Chapter 10, power supplies (primary and secondary power; trouble indication)