Under NFPA 13 2025, which occupancy is normally classified as Light Hazard?

  1. An aircraft hangar
  2. A vehicle parking garage
  3. A general office space
  4. A plastics processing plant
Show the answer

C. A general office space

Offices have low quantity and low combustibility of contents, which fits Light Hazard. Parking garages are Ordinary Group 1, hangars are Extra Hazard Group 1, and plastics processing is Extra Hazard Group 2.

Reference: NFPA 13 2025, occupancy hazard classification chapter and Annex A (Light Hazard examples)

Under NFPA 13 2025, a covered vehicle parking garage is normally which hazard classification?

  1. Light Hazard
  2. Ordinary Hazard Group 1
  3. Ordinary Hazard Group 2
  4. Extra Hazard Group 1
Show the answer

B. Ordinary Hazard Group 1

Parking garages are listed as Ordinary Hazard Group 1 because contents are moderately combustible and fire spread is expected to be moderate. Light Hazard is too low for vehicles with fuel and plastics, and Group 2 is for heavier loads such as machine shops.

Reference: NFPA 13 2025, occupancy hazard classification chapter and Annex A (Ordinary Hazard Group 1 examples)

Which occupancy is a typical example of Extra Hazard Group 1 in NFPA 13 2025?

  1. A church sanctuary
  2. A restaurant dining room
  3. A retail clothing store
  4. An aircraft hangar
Show the answer

D. An aircraft hangar

Aircraft hangars are a standard example of Extra Hazard Group 1, because of the fuel and the large fire a loss could produce. Churches and dining rooms are Light Hazard, and ordinary retail is Ordinary Hazard.

Reference: NFPA 13 2025, occupancy hazard classification chapter and Annex A (Extra Hazard Group 1 examples)