A magnesium shaving fire starts in a machine shop. Which agent is the right type for it?

  1. Class D dry powder agent
  2. ABC dry chemical
  3. Water from a fire hose line
  4. Carbon dioxide gas
Show the answer

A. Class D dry powder agent

Burning magnesium needs a dry powder agent listed for combustible metals, which smothers the fire. Water can react violently with burning metals, and ABC dry chemical and CO2 are not made for them.

Reference: NFPA 10 (2022 edition), Chapter 5

After welding or cutting is finished near combustibles, how long must a fire watch stay under OSHA 29 CFR 1910.252(a)(2)?

  1. At least 5 minutes
  2. At least 30 minutes
  3. At least 2 hours
  4. Until the welder leaves site
Show the answer

B. At least 30 minutes

Hot work can leave smouldering material that flares up later, so the watch continues for half an hour after the work stops. Five minutes is too short to catch a slow smoulder.

Reference: OSHA 29 CFR 1910.252(a)(2) (fire watch)

Under NFPA 10 (2022 edition), what is the highest allowed height for the top of a wall-mounted extinguisher weighing 40 lb or less?

  1. 3.5 feet above the floor
  2. 4 feet above the floor
  3. 6 feet above the floor
  4. 5 feet above the floor
Show the answer

D. 5 feet above the floor

Lighter extinguishers may be hung with the top at 5 ft so people can reach them. The 3.5 ft limit is for extinguishers heavier than 40 lb.

Reference: NFPA 10 (2022 edition), Chapter 6 (installation)