Water supply standpipes itm practice questions

35 questions from the Fire protection and alarm / security practice test.

Start practising

Water supply standpipes itm practice test

10 questions, graded as you go, with the reason for every answer. Start free, no sign-up.

Sample questions

A manual dry standpipe gets its water supply from where?

  1. A permanently connected city main that keeps the risers filled
  2. A rooftop jockey pump that keeps the standpipe pressurized
  3. A pressure tank in the basement
  4. A fire department pumper connected to the fire department connection
Show the answer

D. A fire department pumper connected to the fire department connection

A manual dry standpipe has no permanent water supply; the fire department pumps into the connection when they arrive. A city main or jockey pump would make it an automatic or semiautomatic system.

Reference: NFPA 14 2024, standpipe system types

A standpipe's maximum working pressure is 185 psi. The rule is 200 psi for 2 hours, or 50 psi above the maximum if the maximum is over 150 psi. What hydrostatic test pressure applies?

Answer in psi.

Show the answer

235 psi

Max pressure exceeds 150 psi, so test at maximum + 50 psi. 185 + 50 = 235 psi, held for 2 hours.

Reference: NFPA 14 2024, hydrostatic test

Under NFPA 25 2023, a required sprinkler or standpipe system is out of service. How long can it be out in a 24-hour period before the impairment rules call for evacuation, a fire watch or other interim measures?

  1. 10 hours
  2. 1 hour
  3. 24 consecutive hours
  4. 5 days
Show the answer

A. 10 hours

The trigger is more than 10 hours out of service in any 24-hour period, after which the coordinator arranges evacuation, a fire watch or other temporary protection. One hour is far too short and a full day is too long.

Reference: NFPA 25 2023, Chapter 15 (impairments)