A fire alarm cable must be run through an air-handling plenum with no metal raceway. Under the NEC (NFPA 70) 2023, which listed cable type fits?

  1. FPL
  2. FPLR
  3. FPLP
  4. NPLF
Show the answer

C. FPLP

FPLP is the plenum-rated power-limited fire alarm cable. FPL is for general use and FPLR for risers; neither is listed for plenum use without a raceway.

Reference: NEC (NFPA 70) 2023, 760.154

Under the NEC (NFPA 70) 2023, which Class 2 cable can be used in place of a run that calls for CL2R riser cable?

  1. CL2
  2. CL3X
  3. CL2X
  4. CL2P
Show the answer

D. CL2P

A higher-rated cable can substitute for a lower one, and plenum cable outranks riser cable. General-purpose CL2 and the limited-use X types are lower in the hierarchy.

Reference: NEC (NFPA 70) 2023, 725.154 (cable substitutions)

A straight ladder has a working length of 16 feet. Using the 4-to-1 setting rule, how many feet from the wall should the base of the ladder be set?

Answer in ft.

Show the answer

4 ft

The rule is one foot of base distance for every four feet of working length. 16 / 4 = 4 ft.

Reference: OSHA 29 CFR 1926.1053(b)(5)(i)