A fire alarm cable must be run through an air-handling plenum with no metal raceway. Under the NEC (NFPA 70) 2023, which listed cable type fits?
FPL
FPLR
FPLP
NPLF
Show the answer
C. FPLP
FPLP is the plenum-rated power-limited fire alarm cable. FPL is for general use and FPLR for risers; neither is listed for plenum use without a raceway.
Reference: NEC (NFPA 70) 2023, 760.154
Under the NEC (NFPA 70) 2023, which Class 2 cable can be used in place of a run that calls for CL2R riser cable?
CL2
CL3X
CL2X
CL2P
Show the answer
D. CL2P
A higher-rated cable can substitute for a lower one, and plenum cable outranks riser cable. General-purpose CL2 and the limited-use X types are lower in the hierarchy.
Reference: NEC (NFPA 70) 2023, 725.154 (cable substitutions)