A single homogeneous area of friable sprayed-on ceiling surfacing covers 3,500 square feet. At minimum, how many bulk samples does the AHERA inspection rule call for?
3
7
9
5
Show the answer
D. 5
For surfacing material, 1,000 sq ft or less needs 3 samples, more than 1,000 up to 5,000 sq ft needs 5, and more than 5,000 sq ft needs 7. At 3,500 sq ft the middle tier applies, so 3 is too few.
Reference: 40 CFR 763.86
An inspector samples a homogeneous area of pipe insulation that is not assumed to be asbestos. What is the general minimum number of randomly placed bulk samples?
3
1
5
7
Show the answer
A. 3
Thermal system insulation needs at least 3 randomly distributed samples per homogeneous area. One sample applies only to small patched sections, and 5 and 7 are surfacing tiers.
Reference: 40 CFR 763.86
Which of these is a Category I non-friable asbestos-containing material under NESHAP?
Cement siding panels
Sprayed-on fireproofing
Resilient floor covering
Plaster that has been crushed
Show the answer
C. Resilient floor covering
NESHAP Category I non-friable material is limited to packings, gaskets, resilient floor covering and asphalt roofing products. Cement siding is Category II, and sprayed fireproofing is friable.